PZH R1 25G* is a lightning and surge arrester according to EN 61643-11 ed.2 (IEC 61643-11:2011). It consists of high energy double varistors for better discharge ability and a gas discharge tube connected in series, which ensures zero leakage current through the conductor. Its parameters enable usage in buildings with considerable levels of protection LPL I and LPL II, such as hospitals, banks, industrial and administration complexes, schools, shopping and sports centres or supermarkets. The device is to be installed on the interface of LPZ 0 – LPZ 1 and higher zones according to standard EN 62305 ed.2 (IEC 62305:2010), closest to where overhead line enters the building i.e. in the main distribution boards. S indication specifies a version with remote monitoring.
| System configuration TN-C-S | False |
| System configuration DC | False |
| Nominal voltage AC | 230 V |
| Lightning impulse current (10/350 µs) | 25 kA |
| System configuration IT | False |
| System configuration TN | True |
| Max. continuous voltage AC | 255 V |
| System configuration TN-C | False |
| System configuration TN-S | False |
| System configuration TT | False |
| Number of poles | 1 |
| Voltage protection level | 1,2 kV |